ZX Fire Alarm Control Panels MORLEY-IAS
Commissioning Manual Document No. 996-175-000-1, Revision 01 Page 37
7 Time / Date Option
• Page 2 of the Commission menu is shown below:
[ Panel in Commissioning mode ]
---------------------------------------------
1)Time/Date 2)Program Integrity [n]
3)Power Supplies 4)Passwords
• The Time / Date option allows the various time and date functions to be checked or modified.
• Press ‘1’ from page 2 of the commission menus to select the Time and Date option and show the
current date and time. Then press ‘CHANGE’ and the display then shows a menu of functions
available, as follows:
[ Panel in Commissioning mode ]
---------------------------------------------
CHANGE: 1)Time 2)Date 6)System 7)Crystal
• Select the required option using the numeric keys.
7.1 Time / Date
• These options allow the current date and time to be specified and entered into the panel memory.
• To change the time or date select the appropriate option (Time = 1, Date = 2) and enter the correct
values.
The time is in 24-hour format.
On networked systems, the master panel will automatically set the time and date.
7.2 System (Clear Memory)
• This option allows the system configuration memory to be cleared. The operation returns all
commissioning data to factory default settings.
• To select the option, press ‘6’ and follow the instructions.
WARNING:
This option will completely wipe the configuration memory. All previously entered data
will be lost.
[ Panel in Commissioning mode ]
---------------------------------------------
Do you want to Wipe the WHOLE SYSTEM ?!!
• Press the ENTER key to start to wipe the system.