7. Equivalent Isotropically Radiated Power (EIRP)
7.1. EIRP LIMITS
Revision 3 OneWireless XYR 6000 Transmitter Professional Installation Guide 23
September 2012
Table 7-4 DSSS and ISA100 Transmit Power Settings for the antennas and cable lengths
specified above
Description
Model Selection
Guide Table III
1
Remote
Cable(s)
Length
2
(m)
TX Power Setting
for
ETSI/TNTC/KCC
3
(dBm)
TX Power Setting
for FCC/IC/KOC
/ACMA
/ANATEL
3, 8
(dBm)
TX Power
Setting for
Japan
3, 4
(dBm)
-2 dBi Integral
Antenna
V 0 0 0 0 or S 0 0 0 0 N/A 14 16 10
4 dBi Integral
Antenna
R 0 0 0 0 or H 0 0 0 0 N/A 8 16 10
8 dBi Omni w/o
suppressor
M 0 1 0 0 or M 0 3 0 0
or M 2 1 0 0 or
M 2 3 0 0
1, 3 5 16 N/A
8 dBi Omni w/o
suppressor
M 1 0 0 0 or M 2 9 0 0 10 7 16 N/A
8 dBi Omni with
suppressor
M 0 1 0 1 or M 2 1 0 1 1+1 6 16 N/A
8 dBi Omni with
suppressor
M 0 1 0 3 or M 0 3 0 3
or M 0 3 1 0 or
M 0 3 0 1 or M 1 0 0 3
or M 1 0 1 0 or
M 2 1 0 3 or M 2 3 0 3
or M 2 3 1 0 or
M 2 3 0 1 or M 2 9 0 3
or M 2 9 1 0
1+3, 3+3,
3+10, 3+1,
10+3,
10+10
7 16 10
14 dBi directional
w/o suppressor
6
D 0 1 0 0 or D 0 3 0 0
or D 2 1 0 0 or
D 2 3 0 0
1,3 -2 12 10
14 dBi directional
w/o suppressor
6
D 1 0 0 0 or D 2 9 0 0 10 0 14 10
14 dBi directional
with suppressor
6
D 0 1 0 1 or D 2 1 0 1 1+1 -1 14 10
14 dBi directional
with suppressor
6
D 0 1 0 3 or D 0 3 0 1
or D 0 3 0 3 or D 2 1
0 3 or D2 3 0 1 or
D 2 3 0 3
1+3, 3+1,
3+3
-2 15 10
14 dBi directional
with suppressor
6
D 0 3 1 0 or D 1 0 0 3
or D 2 3 1 0 or
D 2 9 0 3
3+10,
10+3
2 16 10
14 dBi directional
with suppressor
6
D 1 0 1 0 or D 2 9 1 0 10+10 3 16 10
No remote
antenna or cables
option
7
A 0 0 0 0 N/A 0 0 10