RedLINK
TM
Installation Guide (EIM)
69-2091EFS—07 10
15 Compressor off time
(minimum)
5 5 minutes (Heat On/Cool On flashes during off time)
[Options: 0 to 4 minutes]
16 Schedule format Applies only to Model TH6320
0 Weekday/weekend program schedule
1 Weekday/Saturday/Sunday program schedule
17 External fossil fuel kit 1 External fossil fuel kit controls backup heat
0 Thermostat controls backup heat (outdoor sensor required)
18 Dual fuel heat pump
control
1 Droop control**
0 No droop control**
2 Droop control with Aux Heat Lockout**
20 Droop temperature
(dual fuel)
2 Auto temperature droop 2° F (1° C)
[Options: 2 to 5 (2 to 5° F / 1 to 2.5° C)]
21 Dual fuel upstage to
furnace timer
1 1 hour**
[Options: 0 (off) to 16 hours]
22 Outdoor air sensor? 0 No
1 Yes
24 Heat pump
compressor lockout
(balance point)
0 No heat pump compressor lockout**
1 5° F (-15° C) 7 35° F (1.5° C)
2 10° F (-12° C) 8 40° F (4.5° C)
3 15° F (-9.5° C) 9 45° F (7° C)
4 20° F (-6.5° C) 10 50° F (10° C)
5 25° F (-4° C) 11 55° F (13° C)
6 30° F (-1° C) 12 60° F (15.5° C)
25 Heat pump
auxiliary lockout
0 No heat pump auxiliary lockout**
1 5° F (-15° C) 8 40° F (4.5° C)
2 10° F (-12° C) 9 45° F (7° C)
3 15° F (-9.5° C) 10 50° F (10° C)
4 20° F (-6.5° C) 11 55° F (13° C)
5 25° F (-4° C) 12 60° F (15.5° C)
6 30° F (-1° C) 13 65° F (18.5° C)
7 35° F (1.5° C)
26 Auxiliary heat control Applies only to Model TH5320
0 Comfort**
1 Economy
27 Maximum heat
setpoint
90 Max. heat temperature setting is 90° F (32° C)
[Options: 40 °F to 90 °F (4.5 °C to 32 °C)]
28 Minimum cool
setpoint
50 Min. cool temperature setting is 50° F (10° C)
[Options: 50 °F to 99 °F (10 °C to 37 °C)]
32 Temp. display offset
(indoor)
0 Thermostat displays actual temperature
[Options: -3 to +3 °F offset (-1.5 to +1.5 °C)]
33 Temp. display offset
(outdoor)
0 Thermostat displays actual temperature
[Options: -5 to +5 °F offset (-2.5 to +2.5 °C)]
35 Humidity display
offset (outdoor)
3 Thermostat displays actual humidity
[Other options: 0 = -15%, 1 = -10%, 2 = -5%, 4 = +5%, 5 = +10%,
6 = +15% offset]
Setup function Settings & options (factory default in bold)
** See page 11
Installer setup tables

Other manuals for Honeywell RedLINK

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell RedLINK and is the answer not in the manual?

Honeywell RedLINK Specifications

General IconGeneral
BrandHoneywell
ModelRedLINK
CategoryMicrophone system
LanguageEnglish

Related product manuals