Honeywell RTH8580ZW - Heating, Fan, and Changeover Settings

Honeywell RTH8580ZW
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33-00131ES—01 18
System setup
Function Settings & Options
0280
Backlight
0 Backlight off, then on for approximately 45 seconds after keypress.
1 Backlight always on low intensity, full bright after keypress (requires
24VAC connection).
0300
Manual/Auto
Changeover
See page 16 for
more information.
0 Manual changeover (Heat/Cool/Off).
1 Automatic changeover (Heat/Cool/Auto/Off). Automatically turns on Heat
or Cool based on room temperature.
0310
Auto changeover
deadband
3 Heat/cool temperature 3°F apart (1.5°C)
[Other options: 2-9 (2°F to 9°F/1°C to 5°C)])
0320
Temperature
Format (°F/°C)
0 Fahrenheit
1 Celsius
0330
Automatic Daylight
Saving Time
Adjustment
0 Off
1 On
What other functions can I change? (See page 16 for instructions.)
Function Settings & Options
Note: Depending on system settings, functions on this page might not appear.
0180
Heating Fan
Control
0 Gas or oil heat: Use this setting if you have a gas or oil heating system
(system controls fan operation).
1 Electric heat: Use this setting if you have an electric heating system
(thermostat controls fan operation).
0190
Heat Pump
Changeover Valve
(for heat pumps
only)
0 Cooling changeover valve: Use this setting if you connected a wire
labeled “O” to the O/B terminal.
1 Heating changeover valve: Use this setting if you connected a wire
labeled “B” to the O/B terminal.
0220
1st Stage
compressor cycle
rate
3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
0230
2nd Stage
compressor cycle
rate
3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
0240
Heating Cycle
Rate
5 Gas or oil furnace: Standard gas/oil furnace (less than 90% efficiency).
9 Electric furnace: Electric heating systems.
3 Hot water or high-efficiency furnace: Hot water system or gas furnace
(more than 90% efficiency).
1 Gas/oil steam or gravity system: Steam or gravity heat systems.
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0250
Heating Cycle
Rate Stage 2
0260
Heating Cycle
Rate Stage 3
0270
Emergency Heat
Cycle Rate (CPH)
How do I customize my heating/cooling system? (See page 16 for instructions.)