EN2R-9031 0402R15-NE 50
SPECIFICATIONS S4575A, B, P, Q
Model
Suffix A: atmospheric, direct burner ignition
Suffix B: as A but with flame relay output
Suffix P: as A except volatile lock-out
Suffix Q: as B except volatile lock-out
Supply voltage
230 ... 240 Vac, 50/60 Hz (-15%, +10%) or
110 ... 120 Vac, 50/60 Hz (-15%, +10%)
Power consumption
4 VA
Humidity
90% RH max. at 40°C
Ambient temperature
0 ... 60°C
-15 ... 60°C (optional)
Electrical rating (see also note 21.)
Alarm: 230 ... 240 Vac, 50/60 Hz or
110 ... 120 Vac, 50/60 Hz
max 1 mA
Flame relay contact: 230 ... 240 Vac, 50/60 Hz or
110 ... 120 Vac, 50/60 Hz ,
1 A, cos ϕ > 0.6
Flame opto coupler: +5 V, 10 k
Electrical connection
Hot surface ignition relay: 2.8 mm spade terminal
Flame sensing: 4.8 mm spade terminal
PCB connectors: Molex 3003 series suitable for
Molex 3001 female cable
connector
Housing (degree of protection)
See:
accessories for degree of protection page 7..
replacement parts and accessories page 66..
Timing (depending on O.S. number)
Self check time (T
c
): 1.5 s
Glowing time (T
g
): 0 ... 30 s
Safety time (T
s
): 3.5 ... 25 s
Extended ignition time(T
ext
): 0 ... T
s
(depending on elaps of safety time)
Flame sensing
Min flame current:
for optional phase
independent versions: 0.5 µA
for phase dependent
versions: 0.9 µA
Response time on: > 0.2 s
Response time off (T
FR)
:< 1 s
Hot surface ignition
Free contact: 230 ... 240 Vac, 2 A, cos ϕ = 1
24 Vac, 2 A, cos ϕ = 1
110 ... 120 Vac, 2 A, cos ϕ = 1
WARNING
Hot Surface Igniter (HSI) needs to be supplied from a
floating winding of a transformer in order to
quarantee reliable flame detection.
Length flame sensing cable
1 m max.
Length of wiring for external components
1 m max.
Remark
Optional integrated flame relay available with safe separation
or opto coupler with safe separation.
N.C. contact of flame relay has no safe separation.
WARNING
Opto coupler interface needs a debounce time > 20
ms in order to prevent noise caused by transients on
mains.