47 65-0315—02
PII enable Enabled
Disabled
26 23
LCI enable Enabled
Disabled
Interrupted
air switch
(IAS) enable
Enable during purge and
ignition
Disabled
Enable during purge
Interlock
(ILK) start
check enable
No ILK check
ILK check
ILK/IAS open
response
Recycle
Lockout
ILK bounce
detection
enable
Enabled
Disabled
Purge rate
proving
Fan Speed
High Fire Switch
None
Lightoff rate
proving
Fan Speed
Low Fire Switch
None
Prepurge
rate
RPM or % 27 24
Prepurge
time
0-600 seconds
0 = Not configured
Run
stabilization
time
0-600 seconds
0 = Not configured
Standby Rate RPM or %
Postpurge
rate
RPM or %
Postpurge
time
0-600 seconds
0 = Not configured
Forced
recycle
interval time
___hour ___min ___sec
Table 60. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#
Pilot test hold On
Off
28 24
Ignition
source
Hot Surface Igniter
External ignition
Internal ignition
Pilot type Direct burner constant ignition
Direct burner pulsed ignition
Intermittent
Interrupted
Lightoff rate RPM or %
Preignition
time
0-600 seconds
0 = Not configured
Pilot Flame
Establishing
Period
15 secs
10 secs
4 secs
Igniter on
during
1st half of PFEP
Pilot Flame Establishing Period
Main Flame
Establishing
Period
15 secs
10 secs
5 secs
Flame
Threshold
μA/V
Ignite failure
response
Lockout
Recycle
Recycle & hold
Recycle & lockout
29 25
Ignite failure
delay
0-600 seconds
0 = Not configured
Ignite failure
retries
1, 3, or 5
MFEP flame
failure
response
Recycle
Lockout
Run flame
failure
response
Recycle
Lockout
Fan speed
error
response
Recycle
Lockout
Table 60. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#