MAN0905_Issue 7_07/17 Searchpoint Optima Plus with optional HART
®
output
Operating Instructions
2108M0550
39
9. Commissioning using SHC1
Handheld Interrogator
Read this chapter if the SHC1 Handheld Interrogator is being used to communicate
with Searchpoint Optima Plus.
Note:TheinstructionsthatfollowassumethattheSHC1isswitchedon,inOptima+mode,intheMain
Menu.SeeChapter8“UseoftheSHC1HandheldInterrogator”fordetails.
9.1 Introduction
This chapter explains several operations that may be required during commissioning. Only First Time Switch
Onismandatory;Test4-20mALoopIntegrityisrecommended.TheinstructionsassumethattheSHC1is
switchedon,inOptima+mode,intheMainMenu.SeeChapter8“UseoftheSHC1HandheldInterrogator”
for details.
First Time Switch On
Checks that are required on rst power up
Clear Faults or Warnings
How to clear faults or warnings that may be generated during commissioning
Fix the 4-20 mA Output
How to force the mA output to set levels in order to calibrate the controller or to test the
system
Test 4-20 mA Loop Integrity
Check that there is sufcient compliance in the loop to signal alarm and overrange
Caution: After changing any parameter, poll the Searchpoint Optima Plus and verify that the received
value is correct.
9.2 First Time Switch On
Note:SearchpointOptimaPlusissuppliedcalibratedandreadyforuse.Itdoesnotrequirecalibration
during commissioning.
Note:Duringcommissioningthe4-20mAoutputcanbemonitoredeitheratthecontrolroomorlocally
with a multimeter. When connecting or disconnecting a multimeter, power off the Searchpoint Optima Plus,
otherwise the unit will indicate a latched warning that the 4-20 mA loop was broken. If this occurs it can be
clearedusingtheSHC1HandheldInterrogator.
1. Beforeapplyingpowertotheunit,ensurethattheeldwiringiscorrectandallelectricalconnections
are in accordance with Section 4.
2. Applypower.CheckthatthesupplyvoltagetotheSearchpointOptimaPlusisbetween18and32V.
3. Monitorthe4-20mAoutputduringthestartupsequence,whichshouldbeasfollows:-
Current output Duration
<1 mA < 5 s
2 ± 0.2 mA < 60 s
4 ± 0.2 mA ongoing
Note:Ifgasispresent,theunitwillindicateagasreading.