If the unit is signalling Fault or Warning on the 4-20 mA output, the problem should be investigated and
remedied as soon as possible. Some types of faults and warnings will latch the 4-20 mA output and need to
be cleared by a Reset.
1. Select Device Setup.
2. Select Unit Status
3. Select Active Faults or Active Warnings to check for any current faults or warnings.
4. Select View, then First, Next or Previous to display the fault or warning.
Note:Firstdisplaysthefaultorwarningthatoccurredearliestintime.
5. Select Back then Event History to investigate a series of events in more detail.
6. Select Filter, then Warnings or Faults to display the events of interest.
7. Select View, then Latest Log, Older Log or Newer Log to navigate through the table of reported
events.
8. PressBack to return to the Unit Status menu.
9. Use the Problem Solving section of this manual (Chapter 14) to rectify the issue.
10. Press Back to return to the Device Setup menu.
11. Select Test.
12. Select Device Reset.
13. Press OK to initiate a Device Reset, which will clear any latched faults or warnings.
Note:Ifanycongurationchangeshavebeenmade,wait15secondsbeforedoingasoftresetorcycling
the power.
14.Thedisplayshowsaconrmationmessage.PressOK.
15. The display shows a note that the Searchpoint Optima Plus will return to normal operation, press OK.
16. Return to the Welcome screen.