10 5895XL Manual - P/N 151142-L8:L 08/09/2017
Before You Begin Installing Calculating Current Draw and Standby Battery
SK-BEAM-T
3
(with integral test) SLC Standby/Alarm: 2 mA mA mA
Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA
SK-FIRE-CO SLC Standby:
.30 mA mA
Alarm: 7.2 mA mA
Addressable SLC Module
SK-MONITOR Standby/Alarm:
.375 mA mA mA
SK-MINIMON mA mA
SK-PULL-SA mA mA
SK-PULL-DA mA mA
SK-MONITOR-2 Standby/Alarm:
.75 mA mA mA
SK-MONITOR-10 Standby/Alarm:
3.5 mA mA mA
SK-CONTROL SLC Standby:
.375 mA mA
Alarm: .375 mA mA
Aux Pwr Standby:
1.7 mA mA
Alarm: 7 mA mA
SK-CONTROL-6 SLC Standby:
2.25 mA mA
Alarm: 2.25 mA mA
Aux Pwr Standby:
8 mA mA
Alarm: 20 mA mA
SK-RELAY Standby/Alarm:
.255 mA mA mA
SK-RELAY-6 Standby/Alarm:
1.45 mA mA mA
SK-RELAYMON-2 Standby:
1.3 mA mA
Alarm: 24 mA mA
SK-ZONE Aux Pwr Standby 12 mA mA
Alarm 90 mA mA
SLC Standby/Alarm .27 mA mA mA
SK-ZONE-6 Aux Pwr Standby 50 mA mA
Alarm 270 mA mA
SLC Standby/Alarm 2 mA mA mA
SLC Modules
B200SR Sounder Base Aux Pwr Standby: .5 mA mA
Alarm: 35 mA mA
SLC Standby .3 mA mA
B200S Intelligent Sounder Base Aux Pwr Standby: 5 mA mA
Alarm: (high vol) 35 mA mA
SLC Standby .3 mA mA
B200SR-LF Low Frequency Sounder
Base
Aux Pwr Standby: 1 mA mA
Alarm: 125 mA mA
B200S-LF Low Frequency Sounder
Base
Aux Pwr Standby .55 mA mA
Alarm (high vol) 140 mA mA
SLC Standby .30 mA mA
B224RB Relay Base Standby/Alarm: 0.5 mA mA mA
RTS151/151 KEY Alarm: 7.5 mA
mA
RA100Z Alarm: 10 mA
mA
SLC Isolator Devices
SK-ISO (Isolator Module) (100 max/loop) Standby/Alarm: .45 mA mA mA
B224BI Isolator Base Standby/Alarm: .5 mA mA mA
Accessories Modules
Table 2.4 Current Draw Worksheet for SK SLC Devices
Device # of Devices Current per Device
Standby
Current
Alarm
Current