6700 Manual — P/N LS10148-001SK-E:F 8/29/2022 15
Section 3: Prerequisites for Installation
This section of the Manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly,
especially if you are installing a 6700 panel for the first time.
3.1 Inventory
When the 6700 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of the
following:
main circuit board with the display
backbox with door
plastic bag containing two keys, screws, cables, and ten 4.7K ohm end-of-line resistors
manual
3.2 Environmental Specifications
It is important to protect the 6700 control panel from water. To prevent water damage, the following precautions should be FOLLOWED
when you install the units:
Intended for indoor use in dry locations only.
Do not mount the panel directly on exterior walls, especially masonry walls (condensation).
Do not mount the panel directly on exterior walls below grade (condensation).
Protect the panel from plumbing leaks.
Protect the panel from splash caused by Sprinkler System inspection ports.
Do not mount the panel in areas with humidity-generating equipment (such as dryers, production machinery).
When you select a location to mount the 6700 control panel, the unit should be mounted where it will NOT be exposed to temperatures out-
side the range of 32°F-120°F (0°C-49°C) or humidity outside the range of 10%-93% at 86°F (30°C) non-condensing.
3.3 Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you install and program the latest features, we strongly recommend that you down-
load the most current version of software for each product prior to commissioning any System. Contact Technical Support with any ques-
tions about software and the appropriate version for a specific application. The HFSS Honeywell Fire Software Suite is available at
www.silentknight.com.
3.4 Electrical Specifications
Table 3.1 lists the terminal block on the 6700 as well as a description of each individual terminal and their respective electrical rating. For the
location of the terminals, refer to Figure 4.3. See also Section 4 for installation information.
Terminal No.
Label
Description
Rating
Group Individual Voltage Current
Terminal Block 3 TELCO 1 RING Phone Line 1 Telco Ring
TIP Phone Line 1 Telco Tip
PHONE 1 RING Phone Line 1 Phone Ring
TIP Phone Line 1 Phone Tip
TELCO 2 RING Phone Line 2 Telco Ring
TIP Phone Line 2 Telco Tip
PHONE 2 RING Phone Line 2 Phone Ring
TIP Phone Line 2 Phone Tip
Terminal Block 2 RELAY 1 NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
RELAY 2 NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
TROUBLE NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
SLC IN Used for Class A installations 32 VDC 100 mA
+
SLC OUT
SLC terminals 32 VDC 100 mA
+
SLC PROG Used for programming SLC Detectors 32 VDC 100 mA
+
Table 3.1 Terminal Descriptions and Electrical Specifications