26 6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Control Panel Installation AC Power Connection
4.4 AC Power Connection
At installation, connect the AC terminals to the power source as shown in Figure 4.5. It may be necessary for a professional electrician to
make this connection.
AC power for the 6700 is rated at 120VAC, 60Hz, 1.5A.
7
Note: 0.25” spacing must be
maintained between each of these
circuit types; as well as between
power-limited and non-power-limited
circuits.
Figure 4.4 Wire Routing Example
NAC circuits
SBUS
SLC
Phone lines
Relays
Battery
connection
Battery Battery
AC input
!
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF
POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR
INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED
PRI: 120V,
60Hz, BLK-
WHT SEC:
36V, 85VA
YEL-YEL
120V
Figure 4.5 AC Power Connection
supervised AC input
earth
ground

Table of Contents