30 6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Control Panel Installation Wiring Specifications
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The
formula used to generate this chart is shown in the chart below).
The following formulas were used to generate the wire distance chart.
Wiring Distance Calculation Example
Suppose a system is configured with the following SBUS modules:
2 - 5860 Fire Annunciators
1 - 5496 Intelligent Power Expander
1 - 5865 LED Fire Annunciator
1 - 5824 Parallel/Serial Interface
The total worst case current is calculated as follows:
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
22 Gauge 18 Gauge 16 Gauge 14 Gauge
0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft.
0.200 926 ft. 2344 ft. 3731 ft. 5906 ft.
0.300 617 ft. 1563 ft. 2488 ft. 3937 ft.
0.400 463 ft. 1172 ft. 1866 ft. 2953 ft.
0.500 370 ft. 938 ft. 1493 ft. 2362 ft.
0.600 309 ft. 781 ft. 1244 ft. 1969 ft.
0.700 265 ft. 670 ft. 1066 ft. 1687 ft.
0.800 231 ft. 586 ft. 933 ft. 1476 ft.
0.900 206 ft. 521 ft. 829 ft. 1312 ft.
1.000 (Max) 185 ft. 469 ft. 746 ft. 1181 ft.
Table 4.7 Wire Distances Per Wire Gauge
Maximum Resistance (Ohms) = 6.0 Volts
Total Worst Case Current Draw (amps)
Maximum Wire Length (Feet) =
(6000 feet maximum)
Maximum Resistance (Ohms) * 500
Rpu
where: Rpu = Ohms per 1000 feet for various Wire Gauges (see table below)
Wire Gauge Ohms per 1000 feet (Rpu)
22 16.2
18 6.4
16 4.02
14 2.54
Table 4.8 Typical Wire Resistance Per 1,000 ft.
5860 Current Draw = 2 x 0.100 amps = 0.200 amps
5496 Current Draw = 1 x 0.010 amps = 0.010 amps
5865 Current Draw = 1 x 0.200 amps = 0.200 amps
5824 Current Draw = 1 x 0.045 amps = 0.045 amps
Total Worst Case Current Draw = 0.455 amps