EasyManua.ls Logo

Honeywell SILENT KNIGHT 6700 - 7: Conduct a Communicator Test; 8: Manual Alarmnet Registration; 9: Silence Alarms or Troubles; 10: Reset Alarms

Honeywell SILENT KNIGHT 6700
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
94 6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
System Operation Basic Operation
During a Walk Test, the panel’s normal fire alarm function is completely disabled, placing the panel in a local trouble condition. All
zones respond as 1-count zones (responds when a single detector is in alarm) during a Walk Test. Each alarm initiated during the Walk
Test will be reported and stored in the event history buffer.
3. To end the Walk Test, access the main menu. Select 1 for System Test, then press 3 or 4. Press ENTER to end the Walk Test. The system
will reset. The panel will send a “TEST RESTORE” report to the Central Station.
If you do not end the Walk Test manually within four hours, it will end automatically. If there is an alarm or pre-alarm condition in the sys-
tem, you will not be able to enter the Walk Test.
9.3.7 Conduct a Communicator Test
1. From the main menu, press 1 to access System Tests.
2. Select 5 to access Communicator Test.
The screen will display “Manual Communicator Test started”. When the test is completed, you will be returned to the Test Menu. A
manual communicator test requires that at least one daily test in the network be enabled in communicator programming.
3. The manual communicator test will be communicated on both phone lines and Ethernet/cellular paths if they are all programmed. Each
manual communicator test will alternate between one of the phone line paths and one of the AlarmNet paths.
9.3.8 Manual AlarmNet Registration
1. From the main menu, press 1 for System Tests.
2. Select 8 to access Register AlarmNet. The screen will display and ask for confirmation. Feedback will be given if the command was
sent or not.
9.3.9 Silence Alarms or Troubles
1. When an alarm is sounding, press SILENCE and enter your code or rotate the key at the prompt.
If an external silence switch was installed, activating the switch will silence alarms or troubles.
If you are actively using the system menus when you press SILENCE, you do not need to enter your code or rotate the key.
9.3.10 Reset Alarms
Press RESET and enter your code or rotate the key at the prompt. If an external reset switch was installed, activating the switch will reset the
alarms.
Reset Communicator
This options allows the user to reset the communicator. The LCD will display, “Communicator Reset in progress… Please Wait”. You will be
returned to the main menu when the reset is complete.
The communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not allowed if any of the follow-
ing events are active:
•Fire Alarm
Fire Supervisory
Fire Pre-Alarm
CO Alarm
CO Supervisory
9.3.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72.
If the sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a
CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the Central Station receives a detector trouble report (“373” and the zone or point for Contact ID for-
mat; “FT” and the zone or point in SIA format). To check the sensitivity for an individual detector, follow the steps below:
1. From the main menu, press 2 to access Point Functions.
2. Press 2 to access Point Status.
3. Select the desired module.
4. Enter the number of the desired point and press ENTER.
5. A screen similar to those shown below will display.
NOTE: The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to normal, the panel is ready
to access the next device.
NOTE: Alarm and trouble signals that were silenced will resound every 4 or 24 hours, depending on user programming, until the trouble is
cleared.
NOTE: This system has the ability to silence control panels across the EVS network.
NOTE: Multi-Site displays do not reset multiple sites.

Table of Contents

Related product manuals