EasyManua.ls Logo

Honeywell SILENT KNIGHT 6700 - Page 97

Honeywell SILENT KNIGHT 6700
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022 97
Panel Operating Modes System Operation
Table 9.4 describes the behavior of the panel in each of these modes.
Operating
Mode
Occurs When System Behavior In This Mode You Can
Normal No alarm, supervisories
or trouble condition exists
and programming menus
are not in use.
SYSTEM POWER LED is on. The All Systems Normal
display indicates that the system is in normal mode. The
current date and time display on the last line of the LCD.
Enter the appropriate code or rotate the key to
activate the main menu.
Alarm
A smoke detector goes
into alarm or a pull
station is activated.
CO detector goes into
alarm.
If more than 3 categories
are active at a single
time, the screen will
display as shown.
The communicator seizes control of the phone line and
calls the central station.
The onboard annunciator sounds a loud, steady beep
(any notification devices attached to the system will also
sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this one.
Pressing the right arrow key or Info will display the
location macro, date/time stamp, and site/panel number if
applicable.
Pressing the down arrow key to view the type and
location of alarm. (Message will alternate with the
date/time display.)
Press the down arrow key to view the alarm. A
screen similar to this one displays.
Press SILENCE and enter an Access Code (or
activate the key) to silence the annunciator (and
any notification devices attached to the system).
When the alarm condition clears, press RESET
and enter a code (or activate the key) to restore the
panel to normal.
Table 9.4 Panel Operating Modes
Site 1
Model 6700
ALL SYSTEMS NORMAL
08/03/21 01:45:52PM
FIRE: ALRM
Waterflow SW
Zone_1
1 of 1 Info>
Site 1
CO ALRM
[Press for status]
FIRE: ALRM SUPR TRBL
CO: ALRM SUPR
SYS: TRBL
ALARM: MAN_PULL
MODULE_33 POINT_2
ZONE_2
3 of 5
device
type
showing 3 of 5 events

Table of Contents

Related product manuals