EasyManua.ls Logo

Honeywell Silent Knight 6820EVS - 4.17 On-Board Relays (Conventional); 4.18 Remote Station Applications

Honeywell Silent Knight 6820EVS
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Installing 2-Wire Class B Smoke Detectors
To install a Class B two-wire smoke detector, wire as shown in Figure 4.47.
Figure 4.47 Two-Wire Class B Smoke Detector
Installing 2-Wire Class A Smoke Detectors
To install a Class A two-wire smoke detector, wire as shown in Figure 4.48.
Figure 4.48 Two-Wire Class A Smoke Detector Connections
4.15.4 Installing 4-Wire Smoke Detectors
Any compatible UL listed four-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke
detectors). Figure 4.49 and Figure 4.50 illustrate how to connect a UL listed four-wire detector to the control panel.
Installing 4-Wire Class B Smoke Detectors
Figure 4.49 illustrates how to install a 4-wire Class B smoke detector.
Conventions used for wiring 4-wire Class B loops:
1. One Class B 4-wire smoke detector loops can be connected to the control panel.
2. The Class B loop input is paired with a unique power source as shown in Figure 4.49.
Note:
Flexput circuit 5
used as an example.
Either Flexput circuit
5 or 6 could be used.
4.7 kEOL
Supervised
power limited
Supervised
power limited
NOTE: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to refer to the circuit pair. In this
example, Figure 4.48 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.

Table of Contents

Other manuals for Honeywell Silent Knight 6820EVS

Related product manuals