12 32-00006—03
Terminal Functions Min Typical Max Units
T1 Voltage In Range 0.0 - 15.0 VDC Rin=1MOhm
Resolution - 2.43 - mV DC
Null -25.0 - 25.0 mV DC
Accuracy -25.0 - 25.0 mV DC Whichever is
greater
-1.0 - 1.0 %
Out
c
Range 0.0 - 15.0 VDC 10KOhm load
Resolution - 4.0 - mV DC
Null 100.0 - 100.0 mV DC
Accuracy -50.0 - 50.0 mV DC Whichever is
greater
-1.5 - 1.5 %
Current In Range 0.0 - 25.0 mA DC
a
Resolution - 7.4 - uA DC
Null -0.5 - 0.5 mA DC
Accuracy -1.5 - 1.5 % 0 to 25 mA
Out
b,c
Range 0.0 - 25.0 mA DC Max Load =
500 Ω
Resolution - 4.0 - mA Ω
Null -0.5 - 0.5 mA DC
Accuracy -300.0 - 300.0 uA DC 0 to 25 mA
-50 - 50 uA DC 4 to 20 mA
T2 Voltage In Amplitude 0.0 - 15.0 VDC
Trip Point - 3.0 - VDC Comparator
Only
Hysteresis - 0.25 - VDC
Resolution - 0.37 - mV DC
Null -25.0 - 25.0 mV DC
Accuracy -25.0 - 25.0 mV DC
T3 Voltage In Range 0.0 - 15.0 VDC
Resolution - 0.37 - mV DC
Null -25.0 - 25.0 mV DC
Accuracy -25.0 - 25.0 mV DC
Current In Range 0.2 - 25.0 mA DC
Resolution - 3.7 - uA DC
Null -0.5 - 0.5 mA DC
Accuracy -1.5 - 1.5 % 0 to 25 mA
a
T1 input terminal is held at constant 2.5VDC over allowable current
range.
b
Accuracy specification given is for 100 Ω load. Resolution specification
can be converted to mA by dividing out load.
c
Imax=25mA for Vout<10V
Imax=20mA for 10V<Vout<15V
Table 4. Specifications for Basic Cell Functions.