14 32-00006—03
Frequency / PWM
Functions
Min Typical Max Units
PWM Out
T1 Amplitude 5.0 - 10.0 VDC Low output state = 0V
Frequency 100.0 - 1000.0 Hz
Duty Cycle 2.0 - 98.0 %DC 0-100% output allowed
Resolution - 1.0 - %
Accuracy  -0.5  - 0.5 %DC 10V amplitude
Frequency In
T2-
T4
Amplitude 5.0  10.0 15.0 VDC
Range 2.0 - 1000.0 Hz
Min. “on” pulse
width (low %DC)
- 50.0 - usec 10V amplitude
Min. “off” pulse
width (high %DC)
- 130.0 - usec 10V amplitude
Duty
Cycle
2 – 100
Hz
2.0 - 98.0 %DC 10V amplitude
1000 Hz 5.0  - 85.0 %DC 10V amplitude
Resolution  - 1.0 - Hz
Accuracy -5.0 - 0.0 % Whichever is greater
-1.0 - 0.0 Hz
PWM In
T2-
T4
Amplitude
a
5.0  10.0 15.0 VDC
Frequency 125.0 - 500.0 Hz
Min. “on” pulse
width (low %DC)
- 50.0 - usec 10V amplitude
Min. “off” pulse
width (high %DC)
- 130.0 - usec 10V amplitude
Duty
Cycle
125 –
500 Hz
5.0  - 90.0 %DC 10V amplitude
Resolution  - 1.0 %DC
Accuracy 125 Hz -1.5  - 1.5 %DC 10V amplitude
500 Hz -7.5  - 7.5 %DC 10V amplitude
a
Trip points = 3.0V +/- 0.25V
Hysteresis Voltage = 0.5V
Table 6. Specifications for Cell Frequency Functions.