SLATE
FUEL AIR RATIO MODULE 15
R8001C6001
Configuration Min Optimum Range for Performance Max
Thermocouple J -50°C
1025°C ± 4 °C
K -50°C
1000°C ± 4 °C
RTD -135°C
250°C ± 2 °C
NTC 25°C
125°C ± 1°C
Current Out 4 mA
20 mA ± .05 mA
Voltage: In / Out 2 V
10 V 0.3 %,
typical
Table 7. Suggested Sensor Selection Based on Application.
Application Recommended Wire
Size
Recommended
Part Numbers
Communication
Lines
22 AWG two-wire
twisted pair with ground,
or five-wire.
Belden 8723
shielded cable or
equivalent.
Other terminals 18 AWG wire insulated
for voltages and
temperatures for given
application.
TTW60C,
THW75C,
THHN90C
Table 8. Recommended Wire Sizes and Part Numbers.
Resistance to Temperature Conversion Tables
Below are the lookup tables for various types of SLATE sensors.
Linear interpolation is used for values that are between the points
that are shown.
10K NTC
Ohms Degrees C
100.000 228.199
120.000 214.979
144.000 202.439
172.800 190.526
207.360 179.195
248.832 168.404

Related product manuals