EasyManua.ls Logo

Honeywell SLC - MDF-300 Dual Monitor Module; MMF-301 Mini Monitor Module

Honeywell SLC
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 33
Installation Monitor Modules
5.1.3 Dual Monitor Module
MDF-300 Module
The MDF-300 is similar to the MMF-300 but provides for two independent 2-wire IDCs at two
separate, consecutive addresses.
5.1.4 Mini Monitor Module
MMF-301 Monitor Module
The MMF-301 is functionally and electrically identical to an MMF-300, but is offered in a smaller
package for mounting directly in the electrical box of the Style B (Class B) device being monitored.
5.2 Installation
When installing any of these modules DO NOT mix the following services that the IDC provides:
Fire alarm service
Automatic and manual waterflow alarm service with normally open contact devices
Sprinkler supervision with normally open contact devices
fmmtph.wmf
Rotary
Switches
SLC–
SLC+
9 H–
8 H+
7L+
6L–
Address +1
{
Base Address {
Areas used to record the device
address and SLC number.
Figure 5.5 MDF-300 Dual Monitor Module
FMM-101.wmf
Label – Use to record
the device address and
SLC number.
Rotary Switches
IDC (+)
IDC (-)
SLC (+)
SLC (-)
Figure 5.6 MMF-301 Mini Monitor Module

Table of Contents

Related product manuals