EasyManua.ls Logo

Honeywell SLC - 9.6 Wiring Sounder Bases; 9.7 Wiring the W-GATE Wireless Gateway

Honeywell SLC
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Intelligent Detector Bases and Wireless Gateway Wiring a Sounder Base
9.6 Wiring a Sounder Base
Figure 9.4 shows typical wiring of the B200SR or B200SR-LF Sounder Base.
9.7 Wiring the W-GATE
9.7.1 SLC Connections
The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a
LiteSpeed SLC loop on the MS-9200UDLS. It is powered by the SLC loop or by a regulated,
external 24VDC UL-listed power supply. Available wireless devices include a photo detector, a
photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor
module. For details about wireless devices, system setup, and operation, see the SWIFT™ Smart
Wireless Integrated Fire Technology Instruction Manual.
+ -
+ -
+ -
s
lc
-
b
2
0
0
s
r
w
ir
e
.
w
m
f
Figure 9.4 Wiring of a B200SR/B200SR-LF Sounder Base
To next device
on SLC
SLC
Note: The “grid” pattern on the
sounder base has been removed
for illustration purposes only.
UL-Listed
24V Power
Supply
Optional Sounder
Interconnect
NOTE: For more detailed wiring on the sounder base, refer to the device’s installation instructions.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the
Federal Communications Commission (FCC) requirements of the United States Government. It
has not been evaluated for use outside the USA. Use of this system outside the USA is subject to
local laws and rules to which this product may not conform. It is the sole responsibility of the user
to determine if this product may be legally used outside the USA.
NOTE: It is recommended to use the same wire gauge if there are multiple connections to the
same terminal.

Table of Contents

Related product manuals