82 FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Appendix E: Canadian Versions of SLC Devices
UL-listed SLC Device ULC-listed SLC Device Description
Detectors
AD350/AD355 AD350A/AD355A Intelligent detector that combines a photoelectric sensing chamber and fixed
temperature heat detection (135°F/57.2°C).
CP350/CP355 CP350A/CP-355A Addressable, intelligent smoke detector that incorporates an ionization sensing
chamber. Designed to provide open area protection.
SD350/SD355 SD350A/SD355A Addressable intelligent smoke detector that uses a photoelectric sensing
chamber. Listed for use in ducts. Designed to provide open area protection.
SD350T/SD355T SD350TA/SD355TA Adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C).
H350/H355 H350A/H355A Intelligent thermistor sensing circuit for fast response. Designed to provide
open area protection with 50 foot spacing capability. A fixed temperature
sensor with 135°F fixed temperature alarm.
H350R/H355R H350RA/H355RA Incorporates a thermal rate of rise of 15°F (9.4°C).
H355HT H355HTA High temperature sensor with 190°F (87.8°C) fixed temperature alarm.
DNR DNRA Photoelectric Duct Detector, Low-flow. Requires SD350(A)/SD355(A) detector.
Bases
B210LP B210LPA Standard U.S. Low-Profile base (6", 15.24 cm).
B501 B501A Standard European flangeless base (4", 10.16 cm).
B501BH, B501BHT B501BHA, B501BHTA Sounder base, includes Sounder base with temporal sounder (UL 8th Edition).
B501BH-2, B501BHT-2 N/A Sounder base, includes Sounder base with temporal sounder (UL 9th Edition).
B224RB B224RBA Low Profile Intelligent relay base.
B224BI B224BIA Low Profile Intelligent isolator base.
B200SR B200SRA Intelligent sounder base, temporal or steady.
B200SR-LF N/A Intelligent sounder base for low frequency applications
Monitor and Zone Interface Modules
MMF-300 MMF-300A Used for normally open contact alarm initiating devices, such as manual pull
stations, four-wire smoke detectors, heat detectors, waterflow, and supervisory
devices.
MMF-302 MMF-302A Used to interface with two-wire smoke detectors in addition to normally open
contacts.
MDF-300 MDF-300A Two independent 2-wire Initiating Device Circuits (IDCs) at two separate,
consecutive addresses. Wire supervised IDCs as NFPA Style B (Class B) or
Style D (Class A) circuits. The modules come with a thermoplastic cover for
mounting to a 4-inch (10.16 cm) square mounting box.
MMF-301 MMF-301A Functionally similar to the MMF-300 Monitor Module, but offered in a smaller
package for mounting directly in the electrical box of the device being
monitored. (Class B input circuit only.)
BG-12LX BG-12LX An addressable manual pull station with key-lock reset feature. The
addressable module is housed within the pull station.
Control Modules
CMF-300 CMF-300A Control Module, NAC: Addressable Control Module used as Notification
Appliance Circuits (NACs) to power and supervise compatible, UL-listed
notification appliances. Wired supervised NACs as NFPA Style Y (Class B) or
Style Z (Class A). The modules come with a thermoplastic cover for mounting
to a 4-inch (10.16 cm) square mounting box.
CRF-300 CRF-300A Relay Control Module is similar to the CMF-300(A) except used as a Form-C
control relay module.