Page 172 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 13
Screen2 Flow
Scaling Low
[48FSCLLO]
########
Value of the flow custom
engineering unit corresponding
to the LRV of the transmitter.
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
Screen2 Flow
Scaling High
[49FSCLHI]
########
Value of the flow custom
engineering unit corresponding
to the URV of the transmitter.
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
Screen2
Pressure
Custom Unit
[50PCUNIT]

When “Custom” selected for
Screen2 Pressure Units, enter
the custom unit name.
Character string of pressure
custom unit text for display
x = any Alphanumeric value
Press to
enter menu
selection
to select
alphanumeric
character.
to enter
and shift to
the next
character to
the right
Screen2
Pressure
Scaling Low
[51PSCLLO]
########
When “Custom” selected for
Screen2 Pressure Units, enter
the Screen2 Pressure Scaling
Low value.
Value of the pressure custom
engineering unit corresponding
to the LRV of the transmitter
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right