Revision 12 ST 700 SmartLine Pressure Transmitters User’s Manual Page 243
MSG
CODE
AGENCY
TYPE OF PROTECTION
COMM.
OPTION
ELECTRICA
L
PARAMETER
S
AMBIENT
TEMP (Ta)
Class I Zone 2 AEx nA IIC T4 Gc
Ex nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
All
All
-
STANDARDS: CSA C22.2 No. 0-10; CSA C22.2 No. 94-M91; CSA C22.2 No. 25-1966;
CSA C22.2 No. 30-M1986; CSA C22.2 No. 142-M1987; CSA C22.2 No. 157-92; CSA
C22.2 No. 213-M1987; CSA-C22.2 No. 60529:05; CSA-C22.2 No. 60079-0:11; CSA-
C22.2 No. 60079-1:11; CSA-C22.2 No. 60079-11:11; CSA-C22.2 No. 60079-15:12; CSA-
C22.2 No. 60079-31:12; ISA 12.12.01-2010; ISA 60079-0: 2009; ISA 60079-11: 2011; ISA
60079-15: 2009; ISA 60079-26: 2008; ISA-60079-27:2007 (12.02.04)-2006 (R2011); UL
913 Ed. 6; UL 916:1998; ANSI/ISA-12.27.01-2011
C
ATEX
Flameproof: SIRA 12ATEX2233X
II 1/2 G Ex db IIC T6..T5 Ga/Gb
II 2 D Ex tb IIIC T95
o
C…T120
o
C
Db
All
Note 1
T5: -50
o
C TO
85
o
C
T6: -50
o
C TO
65
o
C
Intrinsically Safe: SIRA
12ATEX2233X
II 1 G Ex ia IIC T4 Ga
FISCO Field Device (Only for FF Option)
II 1 G Ex ia IIC T4 Ga
4-20 mA / DE/
HART
Note 2
-50
o
C TO 70
o
C
Foundation
Fieldbus
Note 2
-50
o
C TO 70
o
C
Zone 2, Increase Safety: SIRA
12ATEX4234X
II 3 G Ex ec IIC T4 Gc
4-20 mA / DE/
HART/
Note 1
-50
o
C TO 85
o
C
Zone 2, Intrinsically Safe: SIRA
12ATEX4234X
II 3 G Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
II 3 G Ex ic IIC T4 Gc
4-20 mA / DE/
HART/
Foundation
Fieldbus
Note 2
-50
o
C TO 85
o
C
Enclosure: IP66/ IP67
All
All
-
STANDARDS: EN 60079-0: 2012/A11: 2013; EN 60079-1: 2014; EN 60079-7: 2015; EN
60079-11: 2012; EN 60079-26: 2015; EN 60079-31: 2009
D
IECEx
World
Flameproof: IECEx SIR 12.0100X
Ex db IIC T6..T5 Ga/Gb
Ex tb IIIC T95
o
C…T120
o
C
Db
All
Note 1
T5: -50
o
C TO
85
o
C
T6: -50
o
C TO
65
o
C
Intrinsically Safe: IECEx SIR
12.0100X
Ex ia IIC T4 Ga
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA / DE/
HART
Note 2
-50
o
C TO 70
o
C
Foundation
Fieldbus
Note 2
-50
o
C TO 70
o
C
Zone 2, Increase Safety: IECEx SIR
12.0100X
Ex ec IIC T4 Gc
4-20 mA / DE/
HART/
Foundation
Fieldbus
Note 1
-50
o
C TO 85
o
C
Zone 2, Intrinsically Safe: IECEx SIR
12.0100X
Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
Ex ic IIC T4 Gc
4-20 mA / DE/
HART/
Foundation
Fieldbus
Note 2
-50
o
C TO 85
o
C

Table of Contents