2. Intrinsically Safe Entity Parameters
For details see Control Drawing 50049892.
3. Marking ATEX Directive
The following information is provided as part of the labeling of the transmitter:
• Name and Address of the manufacturer
• Notified Body identification: DEKRA Quality B.V., Arnhem, the Netherlands
• For complete model number, see the Model Selection Guide for the model of pressure transmitter.
The serial number of the transmitter is located on the Meter Body data-plate. The first two digits of the
serial number identify the year (02) and the second two digits identify the week of the year (23); for
example, 0223xxxxxxxx indicates that the product was manufactured in 2002, in the 23rd week
4. Apparatus Marked with Multiple Types of Protection
The user must determine the type of protection required for installation the equipment. The user shall then
check the box [ ] adjacent to the type of protection used on the equipment certification nameplate. Once a
type of protection has been checked on the nameplate, the equipment shall not then be reinstalled using any
of the other certification types.
5. WARNINGS and Cautions:
Intrinsically Safe and Non-Incendive Equipment:
WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN
HAZARDOUS LOCATIONS.
Explosion-Proof/ Flameproof:
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT
Non-Incendive Equipment:
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAYBE PRESENT
WARNING: FOR CONNECTION IN AMBIENTS ABOVE 60
o
C USE WIRE RATED 105oC