Page 64 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 13
Screen2 Flow Scaling
Low
[48FSCLLO]
########
Value of the flow custom
engineering unit corresponding to
the LRV of the transmitter.
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
Screen2 Flow Scaling
High
[49FSCLHI]
########
Value of the flow custom
engineering unit corresponding to
the URV of the transmitter.
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
Screen2 Pressure
Custom Unit
[50PCUNIT]

When “Custom” selected for
Screen2 Pressure Units, enter
the custom unit name.
Character string of pressure
custom unit text for display
x = any Alphanumeric value.
Press to
enter menu
selection
to select
alphanumeric
character.
to enter
and shift to
the next
character to
the right
Screen2 Pressure
Scaling Low
[51PSCLLO]
########
When “Custom” selected for
Screen2 Pressure Units, enter
the Screen2 Pressure Scaling
Low value.
Value of the pressure custom
engineering unit corresponding to
the LRV of the transmitter.
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right