Page 138 SMV800 Modbus User's Guide Revision 1.0
Warnings
Status 2
119
Warnings Status 2
RO
uint8
Bit - 0 Totalizer Reached
Maximum Value
Bit - 1 PT Sensor Over
Temperature
Bit - 2 PT Sensor Input
Open
Bit - 3 PT Sensor Input
Out Of Range
Bit - 4 CJ CT Delta
Warning
Bit - 5 Flow Calculation
Fault
Bit - 6 No Flow Output
Bit - 6 DP/SP/PT/FLOW
Simulation Mode Enabled
Temp. Mod
Debug
Information 1
120
Temperature Module Faults
debug Information 2
RO
uint8
Bit - 0 Temperature
module ADC Reference
Failure
Bit - 1 Temperature
Module Unreliable
Communication
Bit - 2 Temperature
module Factory
Calibration missing
Bit - 3 Temperature
Sensor Over Temperature
Bit - 4 Excess Calibration
Correction
Bit - 5 User Corrects
Activated
Bit - 6 Sensor input bad
Bit - 7 Sensor/CJ Bad
Bit - 8 Sensor Input Failure
Bit - 9 Temperature
Module Low Supply
Press.
Mod.Debug
Information 1
121
Pressure Module Faults
debug Information 2
RO
uint8
Bit - 0 Pressure Sensor
Excess Zero Correction
Bit -1 Pressure Sensor
Excess Span Correction
Bit - 2 Pressure Sensor
Characterization Calc
Error
Bit - 3 Pressure Sensor
Overload
Bit - 4 Pressure Sensor
RAM DB Failure
Bit - 5 Pressure Sensor No
Fact Calib
Bit - 6 Pressure Sensor
Module Unreliable
Communication
Bit - 7 Pressure Sensor
Over Temperature
Bit - 8 Pressure Module
Low Supply
Bit - 9 Reverse Flow is
enabled
Bit - 10 Flow bad for
Negative Square root
Bit - 11 Flow bad for
Divided By Zero