Revision 1.0 SMV800 Modbus User's Guide Page 139
Database
Fault
Information 1
122
Database Fault Information 1
RO
uint8
Bit - 0 NVM copy of
Common database block
found corrupt.
Bit - 1 NVM copy of Vital
Configuration database
block found corrupt.
Bit - 2 NVM copy of
General Configuration
database block found
corrupt.
Bit - 3 NVM copy of
Configuration Change
database block found
corrupt.
Bit - 4 NVM copy of
Advanced Configuration
database block found
corrupt.
Bit - 5 NVM copy of
Display View/Screens
Configuration database
block found corrupt.
Bit - 6 NVM copy of
Display Common
Configuration
database block found
corrupt.
Bit - 7 NVM copy of
Totalizer Configuration
database block found
corrupt.
Database
Fault
Information 2
123
Database Fault Information 2
RO
uint8
Bit - 0 NVM copy of
Miscellaneous
Configuration database
block found corrupt.
Bit -1 NVM copy of
totalizer value block is
found corrupt
Bit - 2 NVM copy of
totalizer value block is
found corrupt
Bit - 3 NVM copy of
advance flow value block
is found corrupt
Bit - 4 NVM copy of
totalizer value back up
block is found corrupt
Bit - 5 NVM copy of user
variables block is found
corrupt
Reserve
124
Reserve Address
NA
NA