Table: Pluto AUS 2-loop battery Calculation - Calculation in Total Sheet
Required Standby Time in Hours
24 Hours
Standby Load Current (Amps)
0,70770 Amps
x
24
=
16,985 Ah
Required Alarm Time in Hours
30 Minutes
Alarm Load Current (Amps)
6,97000 Amps
x
0,5
=
3,485 Ah
Standby and Alarm Load Subtotal
=
20,470 Ah
Derating Factor
=
x 1,25
Total Ampere Hours Required
=
25,59 Ah
Recommended batteries:
BAT-12260 – 26 Ah batteries
Battery Check
The batteries can be housed in the Pluto Cabinet.
Table: Pluto AUS 2-loops Battery Calculation - NAC 1
Device
Qty
Non-Alarm Draw
Total
Qty
Alarm Draw
Total
NAC 1
1
x
0,000000
=
0,000000
1
x
0,500000
=
0,500000
Total Standby Load
0,000000
Total Alarm Load
0,500000
Table: Pluto AUS 2-loops Battery Calculation - NAC 2
Device
Qty
Non-Alarm Draw
Total
Qty
Alarm Draw
Total
NAC 2
1
x
0,000000
=
0,000000
1
x
0,500000
=
0,500000
Total Standby Load
0,000000
Total Alarm Load
0,500000
Table: Pluto AUS 2-loops Battery Calculation - Add on Card
Device
Qty
Non-Alarm Draw
Total
Qty
Alarm Draw
Total
Relay Card
1
x
0,000100
=
0,000100
1
x
0,080000
=
0,080000
OWS DA60 - (Powered by AUX3)
1
x
0,140000
=
0,140000
1
x
3,500000
=
3,500000
DA30
0
x
0,070000
=
0
x
1,800000
=
SDM-4(Powered by AUX3)
1
x
0,024000
=
0,024000
1
x
0,070000
=
0,070000
ARE(Powered by AUX1)
1
x
0,100000
=
0,100000
1
x
0,450000
=
0,450000
Total Standby Load
0,264100
Total Alarm Load
4,100000
Supported ARE list: ASE Romtek, ASE Almos
Used 12 V / 26 Ah batteries Qty of 2nos. Made by AUS CELL No 1. The max. charge current is 1 A. Batteries are fixed for 1 and 2 loop panels.