Page 134 ST 700 Series HART/DE Option User’s Manual Revision 4.0
Online/Device
Setup/Basic Setup/
Device Information
(Continued …)
Device ID
Displays the HART unique long address of the ST
700 Pressure Transmitter
Final Asmbly num
Displays the final assembly number of the ST 700
Pressure Transmitter
Universal rev
Displays the HART Universal Revision of the ST
700 Pressure Transmitter
Fld dev rev
Displays Field Device Revision of the ST 700
Pressure Transmitter
Software rev
Displays the Electronics Board Software Revision of
the ST 700 Pressure Transmitter
Loop mA
Click the Loop Current Mode configuration:
Enable: enables loop current mode (analog
output will operate as a 4 to 20mA signal
consistent with the transmitter output)
Disable: disables loop current mode
(analog output will be fixed at 4mA)
PV Units
Click one of the pre-programmed engineering units.
ST 700 Transmitters with inches of water ranges
are factory calibrated using pressure referenced to
39.2
o
F (4
o
C). Pressure readings can be displayed in
the following engineering units:
inH
2
O inHg ftH
2
O
mmH
2
O mmHg psi
bar mbar g/cm
2
kg/cm
2
Pa kPa
torr atm MPa
inH
2
O @ 4
o
C mmH
2
O@4
o
C inH
2
O @
60
o
F cmH2O mH2O
PV Damping
Enter a value for damping of the device output.
Entries may be any value from 0.00 to 32.00
seconds.
SV Units
Click the relevant unit for measurement of the
Secondary Variable (Meter Body Temperature).
The available measurements are:
o
C ,
o
F,
o
R, Kelvin
Write Protect
Displays the current configuration of the write
protect function. Write Protect is “Enabled” if either
the write protect jumper on the electronics board is
in the ON position or the firmware write protect has
been enabled.