Revision 4.0 ST 700 Series HART/DE Option User’s Manual Page 17
5.3.4 DE-Specific Configuration Parameters
Click the Configure button, and configure parameters according to Table 7.
Table 7 DE Configuration Parameters
Parameter
Read (R) or
Read/Write (R/W)
Configuration Details
LRL
R
Lower Range Limit, Floating Point
URL
R
Upper Range Limit, Floating Point
LRV
R/W
Lower Range Value, Floating Point
URV
R/W
Upper Range Value, Floating Point
PV Units
R/W
Process Variable Units: scaling value selection; default = inches
H
2
0@39
o
F
SV Units
R/W
Secondary Variable scaling units:
o
C or
o
F
Sensor Type
R
Sensor type used in the Transmitter
Damping
R/W
Click digital noise reduction; (see note below)
Span
R
Process Range: URV LRV, Floating Point
Conformity
R/W
Conformity: for the output calculation. Linear (pressure) or
Square Root (flow); (see note below)
Click the Back button to return to the DE MAIN MENU.