Revision 4.0 ST 700 Series HART/DE Option User’s Manual Page 37
Displays Manufacturer of the ST 700 Pressure
Transmitter: Honeywell International
Displays Model number of the ST 700 Pressure
Transmitter: ST 700
Enter the date of site installation. This is a one-time
only configuration.
Displays Meter Body Type of the ST 700 Pressure
Transmitter. Possible types are:
DP: Differential Pressure
AP: Absolute Pressure
GP: Gauge Pressure
Displays the Meter Body ID number of the ST 700
Pressure Transmitter
Enter tag identification up to eight alphanumeric
characters.
Enter a long tag name up to 32 alphanumeric
characters.
Configuration Change Counter: this counter keeps
track of the number of times any configuration
parameter has been changed
Online/Device
Setup/Basic Setup/
Device Information
(Continued …)
Enter a date for user information only.
Enter a descriptor for user information only (up to 16
alphanumeric characters)
Enter a message up to 32 alphanumeric characters)
that will be sent to the Display. The message will be
shown on the Display interspersed with the
configured screens. To stop displaying the message,
click “Clear Display” in the Device Information menu.
Selecting this option clears the “Message” and it will
no longer be sent to the Display.
Displays all of the range information for the device.
The following limits are read only:
LRL: Lower range limit
URL: Upper range limit
LTL: Lower transducer limit
UTL: Upper Transducer limit
The following may be configured to desired zero and
span ranging for the application:
LRV: Lower Range Value (input which
represents 0% output)
URV: Upper Range Value(input which
represents 100% output)
Valid configurations for LRV and URV range from
LTL to UTL.
Displays the full order model number of the ST 700
Pressure Transmitter
Displays the Maintenance mode set by Experion
PKS.
When a HART device requires maintenance, the
engineer or the operator changes the PV Source
value of the corresponding AI channel to MAN. As
soon as the PV Source value is changed for the
channels connected to the ST 700 transmitters,