Revision 4.0 ST 700 Series HART/DE Option User’s Manual Page 41
Online/Device
Setup/Diagnostics
Adv Diagnostics
Displays Advanced Diagnostics details for tracking basic
device operation. For more detailed information on
Advanced Diagnostics, refer to the HART Advanced
Diagnostics section in this Manual. Diagnostic
information includes:
Installation and Device Life details
PV Tracking details
SV Tracking details
TV Tracking details
ET Tracking details
Operating Voltage details
AVDD Tracking details
Sensor CPU Temp. Tracking details
Power Up Diagnostics details
Config History
Displays a history of the last five configuration
parameters that have been changed.
Online/Device
Setup/Services
Write Protection
Displays a picture of the Electronics module to
demonstrate how to connect the hardware write protect
jumper.
Write Protect
Displays the current configuration of the write protect
function. Write Protect is Yes (enabled) if either the
write protect jumper on the electronics board is in the
ON position or the firmware write protect has been
enabled.
Write Protect
On/Off
Configure the firmware write protect option.
Write Protect options are:
Enable: enables the firmware write protect
option (changes in configuration parameters
will not be permitted).
Disable: disables the firmware write protect
option (requires a password).
A 4-digit password is required to change the Write
Protect option from Enabled to Disabled to allow
configuration changes.
The default password is 0000, and can be re-configured
by the user.
Change Password
Change the write protect password to a new 4-digit
code.
Tamper Mode
Displays the current configuration of the Tamper
detection feature (outside attempts to change device
configuration when Write Protect is enabled and Tamper
Mode is Enabled or Tamper Mode alone is Enabled).
Refer to the Tamper Reporting Logic and Write
Protect Logic in Table 13.
Attempt Counter
Displays the number of times a tamper attempt
(configuration write) has occurred. This parameter works
as below:
The attempt counter will get reset on the following
instances:
1. When tamper is reset using the Reset Tamper
Counter method.
When Tamper Mode is configured. During the
configuration, if the Tamper Mode is Enabled and
the other Tamper parameters are configured, then
that is also considered as a Tamper Attempt.

Table of Contents