Poll Address: Click HART short address 0 to 63.
Num req preams: Displays the number of
required request preambles for the ST 700 HART
communications
PV AO: Displays the current value of AO
(analog output) in milliamps
PV AO Alm Type: Displays the current position
of the failsafe jumper on the electronics board
(upscale/ lowscale burnout)
Loop mA: Click the Loop Current Mode
configuration:
Enable: Enables loop current mode (analog
output will operate as a 4 to 20 mA signal
consistent with the transmitter output)
Disable: Disables loop current mode (analog
output will be fixed at 4 mA)
Loop test: This function enables the user to test
the Analog Output measurement at any value
over the full operational range. Click a current
value to apply and verify the current output on
the loop with a calibrated meter.
This function is only available when Loop mA
(Loop Current mode) is Enabled.
D/A trim: perform an analog output calibration at
4.00 and 20.00mA (0% and 100% output).
Displays detailed information pertaining to the
Meterbody, including construction configuration,
materials of construction, fill fluids, and process
connection details.
Displays configured information for each of the eight
display screens. Click a screen number to view details
of the configurations selected in the Screen
Configuration menu.
PV Selection: Click the displayed process
variable as:
o Differential Pressure
o Loop Output
o Percent Output
Pressure Units: Click desired standard
pressure unit.
Number of Decimals: Click the number of
decimal places for the PV display from none to 3.
Custom Tag: Enter a custom tag name for the
screen title up to 14 alphanumeric characters.