Revision 4.0 ST 700 Series HART/DE Option User’s Manual Page 67
5. Set the URV as follows:
a. While observing the PV value at the physical process element (using a sight glass, for
example), adjust the process variable to the desired maximum level, and then click
Set URV.
b. If the displayed value is satisfactory, click Yes to copy the Input Value to the URV in
the Transmitter. If not, click NO and repeat this step.
6. Verify the LRV and URV settings as follows:
a. Open the DE CONFIGURE display, and observe that the settings are established in
Steps 4 and 5.
b. This concludes the procedure to manually set the operating range.