69-2733EFS—05 6
System setup
Function Settings & Options
0165
Restore Schedule
Defaults
0 Continue using programmed schedule.
1 Restore thermostat program to energy saving settings
0170
Select System
Type
If you are not sure of
your heating/cooling
system type or have
other questions,
go to
withermostat.com
1 Heat/cool: Gas, oil or electric heating with central air conditioning.
2 Heat pump: Heat pump without backup or auxiliary heat.
3 Heat only without fan: Gas, oil or electric heat without central air
conditioning.
4 Heat only with fan: Gas, oil or electric heat without central air
conditioning.
5 Heat only (no fan): Gas, oil or hot water heat without central air
conditioning.
6 Cool only: Central air conditioning only.
7 Heat pump: Heat pump with backup or auxiliary heating.
8 Heat/Cool Multiple stages: 2 heat stages (wires on W and W2), 2
cooling stages (wires on Y and Y2).
9 Heat/Cool Multiple stages: 2 heat stages (wires on W and W2), 1
cooling stage (wire on Y).
10 Heat/Cool Multiple stages: 1 heat stage (wire on W), 2 cooling stages
(wires on Y and Y2).
11 Heat pump multiple stages: 2 heat stages (wires on W and W2),
2 cooling stages (wires on Y and Y2) (no aux. heat).
12 Heat pump multiple stages: 3 heat stages (wires on W, W2, and Aux),
2 cooling stages (wires on Y and Y2) (with aux heat).
0173
Heat Pump Type
0 Air to air heat pump
1 Geothermal heat pump
0180
Heating Fan
Control
0 Gas or oil heat: Use this setting if you have a gas or oil heating system
(system controls fan operation).
1 Electric heat: Use this setting if you have an electric heating system
(thermostat controls fan operation).
0190
Heat Pump
Changeover Valve
(for heat pumps
only)
0 Cooling changeover valve: Use this setting if you connected a wire
labeled “O” to the O/B terminal.
1 Heating changeover valve: Use this setting if you connected a wire
labeled “B” to the O/B terminal.
0200
Back-up Heat
Source
0 Electric
1 Fossil fuel
0210
External Fossil
Fuel Kit
0 No
1 Yes
0220
1st stage compres-
sor cycle rate
3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
0230
2nd stage com-
pressor cycle rate
0240
Heating Cycle
Rate
5 Gas or oil furnace: Standard gas/oil furnace (less than 90% efficiency).
9 Electric furnace: Electric heating systems.
3 Hot water or high-efficiency furnace: Hot water system or gas furnace
(more than 90% efficiency).
1 Gas/oil steam or gravity system: Steam or gravity heat systems.
[Other options: 2,4,6,7,8,10,11,12]
0250
Heating Cycle
Rate Stage 2
0260
Heating Cycle
Rate Stage 3
0280
Backlight
0 Backlight off, then on for approximately 8 seconds after keypress.
1 Backlight always on low intensity, full bright after keypress.