Installation Guide
69-2276EFS—01 4
NOTES:
• Minimumupwardslopeofhoseindirectionofsteamflowis2in.perfoot.
• Minimumdownwardslopeofhoseindirectionofsteamflowis3/4in.perfoot.
• Maximumlengthofremotesteamhoseis20ft.
• HeightofP-trapsmustbegreaterthantheductstaticpressure.(Typical3in.
willsuffice.)P-trapmustalsobewetted.
• Minimizesharpbendsandelbows.
PRoPeR Hose installs
AVOIDTHESEINSTALLATIONMISTAKES.