TrueSTEAM Humidification System
7 69-2276EFS—01
Remote mount installation Remote mount installation
M24770
Cuta1-3/4in.diameterducthole,installtheprovided
gasket, and slide the remote nozzle up into the duct.
Secureremotenozzletoductusing#8self-drilling
sheet metal screws (4).
6
Run remote hose from
the humidifier to the duct
nozzle location. Up to 20
ft. of hose can be used.
7
Ifmountingremotelyrequiresrunning
hose through structural barriers (ie. wall
or ceiling), cut at least a hole and slide
hose through. The insulated hose is
2-1/8in.diameter.
Seal off unconditioned space with a
grommet (not provided) or caulk.
8
Minimum 3 in. clearance
required from nozzle outlet to
duct wall.