VISIONPRO
®
8000 WITH WI-FI
®
33-00096—01 14
222 A-L/A Terminal
None
Time Of Day
Economizer
Heat Pump Fault
None Commercial This ISU is only displayed when ISU 101
Application is Commercial.
Note: When the thermostat is setup for
Residential, the L/A terminal operates as
described under "Heat Pump Fault". The L/A
terminal requires no setup for residential
applications.
None: The A-L/A terminal is not used.
Time of Day: The A-L/A terminal is energized
during Occupied periods and when the user
overrides the temperature. The terminal is de-
energized during Unoccupied periods and in
Standby mode.
Economizer: The thermostat controls an
economizer module to provide ventilation
during Occupied periods and free cooling when
outdoor conditions are favorable. The
A-L/A terminal is energized during Occupied
periods and during a call for cooling in
Unoccupied periods. See “Economizer and Time
of Day (TOD) Operation” beginning on page 81.
Notes: The economizer module determines
when outdoor conditions are favorable for free
cooling.
Heat Pump Fault: When 24 volts is detected on
the L/A terminal (compressor monitor), the
thermostat displays a message to alert the user
when the heat pump requires service. The L/A
terminal sends a continuous output to a zone
panel when the thermostat is set to Emergency
Heat mode. The zone panel will not turn on the
heat pump when a zone is set to Emergency
Heat mode.
300 System
Changeover
Manual
Automatic
Manual:
if ISU 101 is
Residential
Automatic:
if ISU 101 is
Commercial
Both Manual: The user must select heating or
cooling as needed to maintain the desired
indoor temperature.
Automatic: The user has the option to select
Auto for the system setting. In Auto mode, the
thermostat controls heating and cooling
equipment as needed to maintain the desired
indoor temperature.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes