VISIONPRO
®
8000 WITH WI-FI
®
19 33-00096—01
313 Radiant Cycles
Per Hour Stage 1
Note: “Stage 1" is
not displayed if
there is only 1
stage of Radiant
Heat.
1 to 12 CPH
3 Both This ISU is only displayed when ISU 201
Heating Equipment is Geothermal Radiant.
The thermostat automatically defaults to the
recommended setting for Geothermal Radiant
Heat (3 CPH).
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load.
314 Cool /
Compressor
Cycles Per Hour
Stage 1
Note: “Stage 1" is
not displayed if
there is only 1
stage.
1 to 6 CPH
3 Both This ISU is only displayed when ISU 207 Cool /
Compressor Stages is set to 1 stage.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load.
314 Cool /
Compressor
Cycles Per Hour
Stage 2
1 to 6 CPH
3 Both This ISU is only displayed when ISU 207 Cool /
Compressor Stages is set to 2 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load.
314 Cool Cycles Per
Hour Stage 3
1 to 6 CPH
3 Commercial This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207
Cool Stages is set to 3 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes