VISIONPRO
®
8000 WITH WI-FI
®
27 33-00096—01
408 Max. Cool
Recovery Outdoor
Temp
Off
-20° F to 100°F
70° F Commercial Off: The cooling system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based on
the rate that the cooling system can recover at
for a mild day in your region. Default setting is
6° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to be
associated with the Maximum Recovery Ramp
Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature.
409 Adaptive Recovery
No
Yes
Yes Residential No: The system will begin heating or cooling
recovery at the scheduled time.
Yes: The thermostat will begin heating or
cooling recovery early to ensure that the
temperature is reached at the scheduled time.
The thermostat will adjust the start time of the
equipment based on how quickly the scheduled
temperature was reached on previous days. See
page 52 for more information on Adaptive
Intelligent Recovery.
410 Minimum Cool
Setpoint
50° F to 99° F
50° F Both The user cannot set the temperature below this
level.
410 Maximum Heat
Setpoint
40° F to 90° F
90° F Both The user cannot set the temperature above this
level.
411 Keypad Lockout
Unlocked
Partially Locked
Fully Locked
Unlocked Both Unlocked: User has access to all thermostat
settings.
Partially Locked: User can modify only
temperature settings.
Fully Locked: User cannot modify any settings.
500 Wired Sensor on
S Terminals
No
Yes
No Both This ISU is only displayed if ISU 106 was
configured to Wired/Internet.
Select Yes if a wired indoor, outdoor, or
discharge sensor is wired to S1.
500 Wired Remote
Indoor Sensor
No
Yes
No Both Select Yes if a wired indoor sensor is wired to
S1.
500 Wired Outdoor
Sensor
No
Yes
No Both Select Yes if a wired outdoor sensor is wired to
S1.
500 Wired Discharge
Sensor
No
Yes
No Both Select Yes if a wired discharge sensor is wired
to S1
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes