VISIONPRO
®
8000 WITH WI-FI
®
33-00096—01 28
501 Indoor Sensor
Name
[Select Indoor Sensor Name]
Indoor Sensor Both Select a name (location) of the Wired Remote
Indoor Sensor.
502 Indoor Sensor
S1
Both Confirms type of sensor wired to S1.
503 Indoor Sensor
Type
10K
20K
10K:
if ISU 101
Application is
Residential
20K:
if ISU 101:
Application is
Commercial
Both Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-A
must be used in combination with a TR21
sensor or another TR21-A sensor for the
thermostat to calculate the correct indoor
temperature reading).
See “Wiring guide — Wired Indoor Sensors”
beginning on page 88 for information on the
sensor type you should select based on how the
sensors are wired. For example, you would
select 20K when you have two TR21-A (10K)
sensors wired in series.
504
Use [T-Stat Sensor]
for Temp Ctrl
Use T-Stat Sensor for Temp Ctrl -
Yes or No
Sensors are
Averaged (T-Stat
Sensor and Remote)
Both Only displayed when a wired indoor sensor is
configured. Select Yes if you want the
thermostat to average with wired indoor sensor.
Select No if you want to sense temperature only
at the wired sensor.
505 Outdoor Sensor
S1
Both Confirms type of sensor wired to S1.
509 Discharge Sensor
S1
Both Confirms type of sensor wired to S1.
510 Discharge Sensor
Type
10K
20K
10K Both Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
511 A-Coil Low Temp.
Cutoff
Off
35° F to 65° F (in 5° F
increments)
Off Both If an optional Discharge Sensor is used, this
feature can help prevent icing on the air
conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system fan
continues to run, until the temperature rises to a
safe level.
700 Filter Type
None
Elec. Air Cleaner
Media
Media Both
702 Number of Air
Filters
1 to 2
1 Both
711 Air Filter 1
Reminder
Note: “1” is not
displayed if there
is only 1 filter.
Off
Run Time:
10, 20, 30, 45, 60, 90, 120, 150
days
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months
Off Both
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes