VISIONPRO
®
8000 WITH WI-FI
®
33-00096—01 32
912 User Dehumidifier
in Heat Mode
Use Dehumidifier
in Cool Mode
Use Dehumidifier
in Off Mode
User Dehumidifier in Heat Mode
- No or Yes
Use Dehumidifier in Cool Mode -
No or Yes
Use Dehumidifier in Off Mode -
No or Yes
Use Dehumidifier in
Cool Mode - Yes
Default varies based
on heating/cooling
equipment selected
Both This ISU is only displayed when ISU 900 Dehum
Equipment is set to Dehumidifier.
Heat: Includes Heat, Emergency Heat and Auto.
If the system is in Auto mode, the thermostat
will allow dehumidification if the last call was for
heat.
Cool: Includes Cool and Auto. If the system is in
Auto mode, the thermostat will allow
dehumidification if the last call was for cool.
Off: The thermostat will allow dehumidification
when the system setting is Off.
See “Dehumidification - Residential” beginning
on page 60 or “Dehumidification - Commercial”
beginning on page 64.
913 Dehum Fan
Control
Tstat Controls Fan
Equip Controls Fan
Tstat Controls Fan Both This ISU is only displayed when ISU 900 Dehum
Equipment is set to Dehumidifier.
Tstat Controls Fan: The thermostat turns on the
dehumidifier and the fan when dehumidification
is needed.
Equip Controls Fan: The thermostat turns on the
dehumidifier when dehumidification is needed.
The fan is controlled by the equipment.
914 Run Dehumidifier
when Cool is On
Yes
No
Yes Both This ISU is only displayed when ISU 900 Dehum
Equipment is set to Dehumidifier.
Yes: Dehumidifier can run when the cooling
system is on.
No: Dehumidifier can NOT run when the cooling
system is on.
918 Dehum Away
Mode
Not Allowed
Allowed
Not Allowed Both This ISU is NOT displayed when ISU 900
Dehum Equipment is None.
ISU 919 to 920 are only displayed when ISU
918 Dehum Away Mode is Allowed.
See “Dehumidification Away Mode” beginning
on page 63.
919 Dehum Away
Mode Fan Setting
Automatic
On
Circulate
Automatic Both The On and Circulate settings may re-introduce
humidity into the living space.
920 Dehum Away
Mode Low Limit
Temp
70° F to 80° F
76° F Both If the cooling system is used to control humidity
while Dehumidification Away Mode is active, the
thermostat allows the cooling system to lower
the indoor air to the Low Limit Temperature
Setting to reach the dehumidification setting at
ISU 920.
920 Dehum Away
mode Temp
Setting
70° F to 99° F
85° F Both The temperature maintained while
Dehumidification Away Mode is active and the
desired humidity level is satisfied.
920 Dehum Away
mode Dehum
Setting
40% to 70% (in 5% increments)
65% Both The desired humidity level while
Dehumidification Away Mode is active.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes