VISIONPRO
®
8000 WITH WI-FI
®
33 33-00096—01
921 Dehumidifier Filter
Reminder
Off
30, 60, Calendar Days
3 to 12 Calendar Months (in 1
month increments)
Off Both
1000 Ventilation Type
None
ERV / HRV
Passive (Fan Only)
Fresh Air Damper
None Both None: The thermostat does not control
ventilation.
ERV/HRV: The thermostat controls an Energy
Recovery Ventilator or Heat Recovery Ventilator
for ventilation.
Passive (Fan Only): The thermostat turns on the
fan for ventilation.
Fresh Air Damper: The thermostat turns on the
fan and opens a fresh air damper for ventilation.
1002 Ventilation Wiring
None
U1
Thermostat defaults
to the unused
universal terminal
U1.
Both Number of Universal Outputs:
TH8321 Thermostat: U1 terminals
U1 are dry contacts that require power. See
“Wiring IAQ Equipment or a Heat/Cool Stage to
the Universal Terminals” beginning on page 86.
1005 Ventilation
Method
ASHRAE
Percent On Time
Defaults to
ASHRAE
when ISU 101
Application is set to
Residential.
Percent on Time is
the only choice when
ISU 101 Application
is set to Commercial.
Both See “Ventilation Control Methods (ISU 1005)”
beginning on page 68.
1006 Vent Fan Control
Tstat Controls Fan
Equip Controls Fan
Tstat Controls Fan Both Tstat Controls Fan: The thermostat turns on the
ventilation equipment and the fan when
ventilation is needed.
Equip Controls Fan: The thermostat turns on the
ventilation equipment when ventilation is
needed. The fan is controlled by the equipment.
1009 Number of
Bedrooms
1 to 6
2 bedrooms Residential This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
1009 Size of House
1000 to 5000 sq. ft. (in 100 sq.
ft. increments)
(90 to 460 sq. m.)
1000 sq. feet Residential This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
1010 Ventilation Rate
30 to 350 CFM (in 5 CFM
increments)
(850 - 9900 LPM)
150 Residential This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
1012 Vent Percent On
Time
10% to 100% (in 10%
increments)
30% Both The thermostat operates ventilation equipment
based on a percentage entered in the installer
setup (ISU 1012). For example, if Percent on
Time is set to 50%, the ventilation equipment
will run at random times during a 1 hour period
until it reaches a 50% run time (approximately
30 minutes).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes