VISIONPRO
®
8000 WITH WI-FI
®
33-00096—01 62
Fig. 131.
2. Select the terminals wired to the Whole House Dehumid-
ifier. See Fig. 132.
Fig. 132.
3. Select the system mode(s) to allow dehumidification.
See Fig. 133.
NOTE: Heat includes Heat, Emergency Heat and Auto.
If the system is in Auto mode, the thermostat
will allow dehumidification if the last call was for
heat.
Cool includes Cool and Auto. If the system is in
Auto mode, the thermostat will allow dehumidifi-
cation if the last call was for cool.
Fig. 133.
4. Set Dehumidifier Fan Control settings. See Fig. 134.
Tstat Controls Fan
Thermostat turns on the dehumidifier and the fan
when dehumidification is needed.
Equip Controls Fan
Thermostat turns on the dehumidifier when
dehumidification is needed. The fan is controlled by
the equipment.
Fig. 134.
5. Set the desired lockout option. See Fig. 135.
Fig. 135.
NOTE: ISU 1014 gives the option to lockout ventilation
during calls for dehumidification. This helps
maintain the desired humidity level.