Section 5 – Data Field Descriptions
5-11
FIELD TITLE and DATA ENTRIES EXPLANATION
1*53
Disable Download Callback
0 = callback required
1 = no callback required
Select whether a callback from the control panel is required for downloading.
Must be set to0” for Commercial Fire and Burglary installations.
1*55
European Date Format
0 = disable (mm/dd/yy)
1 = enable (dd/mm/yy)
Select the date format for display in the event log.
1*56
AC 60Hz or 50Hz
0 = 60Hz
1 = 50Hz
Select the frequency for the AC.
Must be set to 0 for U.S. and Canadian installations.
1*57
Enable 5800 RF Button Global
Arm
0 = disable
1 = enable
If enabled, the system arms/disarms in accordance with the button’s user’s
global arming settings.
Must be 0 for Commercial Fire and Commercial Burglary installations.
1*58
Enable 5800 RF Button Force
Arm
0 = disable
1 = enable
If enabled, allows the RF button user to force a bypass of all faulted zones
when arming the system.
NOTE: When attempting to arm the system, the keypad beeps once after the
button is pressed if any faulted zones are present. The user should then
press the button again within 4 seconds to force-bypass those zones and arm
the system.
NOTE: Force Arm is not approved for ULC applications.
1*60
Zone 5 Audio Alarm Verification
0 = disable
1 = enable
If enabled, zone 5 is used for 2-way audio (AAV).
Must be set to0” for UL commercial fire and burglary installations.
NOTE: Zone 5 cannot be used as protection zone.
1*61
Abort Verify
0 = disable
1 = enable
If enabled and an alarm occurs on a non-fire zone, the system displays
“ALARM ABORTED”, if a user enters the code + off sequence during the
Abort Window (field *88).
1*70
Event Log Types
0 = disable
1 = enable
This field has five entries as follows: Alarm, Check, Bypass, Open/Close, and
System. If enabled, the system logs those events into the event log.
1*71
12/24 Hour Type Stamp Format
0 = 12-hour
1 = 24-hour
Select the type of time stamping for the event log.
1*72
Event Log Printer On-Line Mode
0 = disable
1 = enable
If enabled, the system prints the events as they occur.
If disabled, the system prints the log only upon request.
1*73
Printer Baud Rate
0 = 1200
1 = 300
Select the baud rate for the serial printer.
1*74
Relay Timeout XXX Minutes
Enter 000-127 times 2 minutes (000-254).
This is used for #80 Menu Mode Time-Driven event relay command numbers
“04/09” and Output Programming in the #93 Menu Mode Programming output
command “56.”
1*75
Relay Timeout YYY Seconds
Enter 000-127 seconds.
This is used for #80 Menu Mode Time-Driven event relay command numbers
“05/10” and Output Programming in the #93 Menu Mode Programming
command “57.”