USER GUIDE
Item#: INPN2, INPN1.75, INPN1.125, INPNK
OVERVIEW
The In-line Pitotless Nozzle can be used for: stairwell standpipe flow testing, pressure reducing valve flow
testing, fire pump flow testing, fire flow testing of hydrants, or as an in-line flow meter for fire pumps. The
device connects to 2 ½” outlets. Hose or piping can be attached downstream of the unit without affecting the
accuracy of the readings. The In-Line Pitotless Nozzle determines flow-rate by measuring the differential
pressure between the two gauge ports.
COMPONENTS (INCLUDED IN KIT)
1) Line Gauge. 0-200 psi, 2 1/2" dial, 1% full scale accuracy rated.
2) Pitotless NozzleThreaded. Sizes: 1⅛”, 1 ¾”, or 2”.
3) Differential Chamber. 2 ½” NH Female Swivel x 11”.
4) Differential Gauge. ½% full scale accuracy rated; 0-100 PSI.
5) Gauge Tubes. Two 12” tubes w/ push-to-connect tube fittings and male quick disconnects.
6) Discharge Valve. 2 ½” NH Slow close valve for controlling water discharge. Included in kit.
OPTIONAL ACCESSORIES (NOT INCLUDED)
7) 2 ½” Stream Shapers. To minimize hose-burn.
8) 30° or 45° Elbows. To angle the hose or the In-line Pitotless Nozzle to meet job conditions.
9) Spanner Wrench. To tighten swivel couplings.
Question and Answer IconNeed help?

Do you have a question about the Hose Monster INPN1.75 and is the answer not in the manual?

Hose Monster INPN1.75 Specifications

General IconGeneral
BrandHose Monster
ModelINPN1.75
CategoryTest Equipment
LanguageEnglish

Summary

Operation

Flow Charts

Maintenance

Female Quick Disconnect Fittings Maintenance

Lubricate and maintain female quick disconnect fittings to prevent corrosion.

Differential Gauge Maintenance

Refer to manufacturer for operation and battery replacement; calibration available.

Line Gauge Calibration

Recommended annual certification and calibration to NIST standard.

Pitotless Nozzle and Differential Chamber Cleaning

Wipe down with a damp rag after each use to remove dirt and debris.

Tips