Chapter 4
System Specifications
Electrical Specifications
120
NOTE A qualified electrician must wire the PDCA receptacle to site power using copper wire and in
compliance with all local codes.
Each branch circuit used within a complex must be connected together to form a common ground.
When only one PDCA is to be installed in a system cabinet, it must be installed as PDCA0. Refer to Figure 4-1
for PDCA0 location.
NOTE When wiring a PDCA, phase rotation is unimportant. When using two PDCAs, however, the
rotation must be consistent for both.
a. A dedicated branch circuit is required for each PDCA installed.
Table 4-7 Option 6 and 7 Specifics
PDCA
Part Number
Attached Power Cord Attached Plug
Receptacle
Required
A5201-69023
(Option 6)
OLFLEX 190 (PN 600804) is a 2.5 meter multi
conductor, 600 volt, 90 degree C, UL and CSA
approved, oil resistant flexible cable. (8 AWG 60 A
capacity)
Mennekes
ME 460P9
(60 A capacity)
Mennekes
ME 460R9
(60 A capacity)
A5201-69024
(Option 7)
H07RN-F (OLFLEX PN 1600130) is a 2.5 meter
heavy duty neoprene jacketed harmonized
European flexible cable. (4 mm
2
32A capacity)
Mennekes
ME 532P6-14
(32A capacity)
Mennekes
ME 532R6-1500
(32 A capacity)