Power cable specications (continued)
Cross-sectional area 4 mm² or 12 AWG
Terminals Ferrule terminals, except the PE terminal, which uses the M6 ring type
External diameter range 8.5–14 mm
NOTE: The main disconnect and branch protection should be provided by the installer.
Conguration 2: 200–240 V line-to-line one-phase conguration
Printer specications
Number of power lines 2 lines + PE
Input voltage (line to line) 200–240 V~ (±10%)
Input frequency 50/60 Hz
Power consumption (typical) 2.6 kW
Maximum load current (per phase) 19 A
Branch circuit breaker specications
2 poles, 25 A, type J
Power cable specications
Conguration 2 lines + PE
Cross-sectional area 4 mm² or 12 AWG
Terminals Ferrule terminals, except the PE terminal, which uses the M6 ring type
External diameter range 8.5–14 mm
Power cables
No power cable is provided with the processing station. The cables that you use must meet the minimum
specications for the chosen conguration explained for each conguration.
32 Chapter 3 Site preparation requirements for the processing station ENWW