HP ProLiant DL380 Generation 3 Server High-Density Deployment
16
Table 8. HP PDUs
Part
Number
Availability
Input
Voltage
Current
Rating
Maximum
Servers per
PDU
Input
Connectors
and Cord
Output
Connectors
Output
Breakers
Dimensions
Weight
Modular PDUs (Up to 32 outlets, 0U/1U mounting)
252663-B24
3
Worldwide High
16 A 10 Detachable
input
cord; IEC 320
C-20
16 X IEC320-C13 2 x
10
A
444.5 x41.2 x 142.2
mm
(7.5 x 1.62 x 5.6 in)
8.16 kg
(18 lb)
252663-D71
3
North
America,
Japan
Low 24 A 8 NEMA L5-30P
12-ft cord
32 × NEMA 5-15R 4 ×
15
A
444.5 x 41.2 x 142.2
mm
(7.5 x 1.62 x 5.6 in)
8.16 kg
(18 lb)
252663-D72
3
North
America,
Japan
High 24 A 16 NEMA L6-30P
12-ft cord
32 × IEC 320-C13 4 ×
15
A
444.5 x 41.2 x 142.2
mm
(7.5 x 1.62 x 5.6 in)
8.16 kg
(18 lb)
252663-B31
3
International High 32 A 21 NEMA L6-30P
12-ft cord
32 × IEC 320-C13 4 ×
15
A
444.5 x 41.2 x 142.2
mm
(7.5 x 1.62 x 5.6 in)
8.16 kg
(18 lb)
252663-B21
2,3
Worldwide High 40 A 27 Hardwired
24 × IEC 320-C13
4 × IEC 320-C19
4 ×
15
A
444.5 x 41.2 x 142.2
mm
(7.5 x 1.62 x 5.6 in)
8.16 kg
(18 lb)
Dual Input PDUs (12 Outlets, built-In Transfer switch, 0U/1U mounting)
191186-001
1
North
America
High 24 A 16 x2 NEMA L6-
30P
12-ft cord
12 × IEC 320-C13 4 ×
10
A
4.37 x 43.18 x 38.74
cm
(.72 x 17 x 15.25 in)
9.1 kg
(20 lb)
191186-B31
1
International High 30 A 20 x2 IEC 309-32A
12-ft cord
12 × IEC 320-C13 4 ×
10
A
4.37 x 43.18 x 38.74
cm
(1.72 x 17 x 15.25 in)
9.1 kg
(20 lb)
Note 1: This PDU supports power from two different sources. If one power source fails, the PDU uses the alternate source.
Note 2: This PDU must be hard-wired to the power source by a certified electrician.
Note 3: This PDU is using the maximum rated power supply input and not the derated values.
Figuring Type and
Number of PDUs
The type and number of PDUs required to power a full rack of servers depends on the power
requirement for each server, the number of servers deployed in the rack, and the available power for
the servers.
HP PDUs support both high-voltage and low-voltage applications. The input current rating for a
ProLiant DL380 Generation 3 server is either 2.3 A at 240 volts or 4.9 A at 115 volts. To determine
the number of servers supported by a PDU, divide the current rating of the PDU by the total input
current rating of the server.
IMPORTANT: The examples shown in the following sections use the maximum rating of the power supply.
They are for reference only.