SpecificationSpecification ValueValue
Input requirementsInput requirements
Rated input voltage -40 VDC to -72 VDC
-48 VDC nominal input
Rated input current 24 A at -40 VDC input
19 A at -48 VDC input, nominal input
12.4 A at -72 VDC input
Rated input power (W) 874 W at -40 VDC input
865 W at -48 VDC input, nominal input
854 W at -72 VDC input
Rated input power (BTUs per hour) 2,983 at -40 VDC input
2,951 at -48 VDC input, nominal input
2,912 at -72 VDC input
Power supply outputPower supply output
Rated steady-state power (W) 800 W at -40 VDC to -72 VDC
Maximum peak power (W) 800 W at -40 VDC to -72 VDC
Maximum peak power 800 W at 200 VAC to 277 VAC input
800 W at 380 VDC input
WARNING:WARNING: To reduce the risk of electric shock or energy hazards:
This equipment must be installed by trained service personnel.
Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit has no direct connection to
a primary circuit and derives its power from a transformer, converter, or equivalent isolation device.
The branch circuit overcurrent protection must be rated 27 A.
CAUTION:CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to the
earthing conductor at the equipment.
If this connection is made, all of the following must be met:
This equipment must be connected directly to the DC supply system earthing electrode conductor or to a bonding
jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode conductor is connected.
This equipment must be located in the same immediate area (such as adjacent cabinets) as any other equipment that
has a connection between the earthed conductor of the same DC supply circuit and the earthing conductor, and also the
point of earthing of the DC system. The DC system must be earthed elsewhere.
The DC supply source is to be located within the same premises as the equipment.
Switching or disconnecting devices must not be in the earthed circuit conductor between the DC source and the point of
connection of the earthing electrode conductor.